Indoor panels |
|
|
• |
Type ELGAN 40 |
|
|
|
|
Rated current of main busbar In [A] |
up to 4000 |
|
Rated current of the distribution bar In [A] |
up to 1600 |
|
Rated insulation voltage Ui |
1000 |
|
Rated impulse withstand voltage Uimp [kV] |
8 |
|
Rated operational voltage Ue [V] |
690 |
|
Rated short-time current main busbar Icw |
130 kA / 1s |
|
This modular switchboard system offers solutions for almost every standards by the use of variable panel dimensions (grid-dimension 12,5 mm).
The ELGAN 40 switchboard system is based on a line of type-tested standard control panels, which were tested with Siemens, ABB, Schneider Electric, Mitsubishi, Rittal and Jean Müller circuit-breakers and fuse-circuit- breaker-blocks.
The assembly in the outgoing panels can be applied in horizontal or vertical way.
By the use of the circuit-breaker-module for the slim-line outgoing panel we provide you the possibility to combine fuse-circuit-breakerblocks (NH00 to NH3) with compact-circuit breakers (up to 630A) in one panel.
3- or 4-pole main busbar system with PE-busbar system in blank, lacquered or isolated achievement (shock protected).
4-pole cable connecting bar system for the connection of cables up to 300mm².
Accessories for the system :
Align fixation, floor panels, angles, connectors, system covers. Furthermore stand bases in different measures are possible.
|
|
Advantages |
• |
Type-tested switchboard system |
• |
Reference operating current up to 5000A |
• |
Reference temporary current-carrying capacity up to 100 kA/1s |
• |
Plug-ins up to 500A power rating |
•
|
The variable built-in option of the assembly panel with regard to the plug-ins enables the utilization of all components produced by various manufacturers |
• |
The exchangeable MCC plug-ins facilitate rapid repairs and short downtimes in compliance with technical requirements |
|
Some Technical Features |
• |
The Logstrup Draw-Out System is a completely modular type-tested switchboard system |
• |
It has variable plug assignment with very high contact pressure |
• |
The inner subdivision can be executed from Form 1 to Form 4 |
• |
Area of application: Industrial systems with powerful technical requirements, e.g. power stations, sewage works |
|
|
|
|